FTP CAT 6 LSOH
Product Name/Code: FTP Cat 6 LSOH
Performance
Application: Frequency RL Attenuation NEXT PSNEXT
100 Base-T4 (MHz) (dB) (dB/100m)  
100 Base-TX min. max min (dB)
(dB)
100VG - AnyLAN 1.000 20.00 2.00 74.30 72.30
1000 Base-T (Gigabit Ethernet) 4.000 23.00 3.80 65.30 63.30
155 Mbps ATM 8.000 24.50 5.30 60.80 58.80
622 Mbps AT 10.00 25.00 6.00 59.30 57.30
Reference Standard 16.00 25.00 7.60 56.20 54.20
EIA/TIA 568B & ISO/IEC 11801 20.00 25.00 8.50 54.80 52.80
Cable Construction
25.00 24.30 9.50 53.30 51.30
Conductor Solid Bare Copper 31.25 23.60 10.70 51.90 49.90
AWG 23 62.50 21.50 15.40 47.40 45.40
Conductor Diameter(mm) 0.574 100.00 20.10 19.80 44.30 42.30
Insulation Solid PE 200.00 18.00 29.00 39.80 37.80
250.00 17.30 32.80 38.30 36.30
Average Thickness (mm) 0.2 Frequency ELFEXT PSELFEXT
ACR
Insulation Diameter(mm) 0.95 (MHz)    
Drain wire Tinned copper min (dB) min (dB)   (dB)
Construction (mm) 7/0.2 1.000 67.80 64.80 72.30
Al foil Aluminium/PET fiol 4.000 55.80 52.80 61.50
    8.000 49.70 46.70 55.50
    10.00 47.80 44.80 53.30
Sheathing LSOH /LSFROH 16.00 43.70 40.70   48.60
Thickness(mm) 1.1 20.00 41.80 38.80 46.30
Diameter(mm) 6.1 25.00 39.80 36.80 43.80
    31.25 37.90 34.90 41.20
Core Identificatin/Color Code According to customer request 62.50 31.90 28.90 32.00
Bending Radius 6xOverall Diameter 100.00 27.80 24.80 24.50
    200.00 21.80 18.80 10.80
250.00 19.80 16.80 5.50
   
Electrical Performance
Fire Performance Max.Conductor DC Resistance at 20 ℃(Ω/Km) <93.8
Flame propagation Test to IEC 60332 Part 1(LSOH)
Flame Propagation Test to IEC 60332 Part 1 and Part 3(LSFROH)
Emission of Halogen Acid Gas to IEC 60754 Part 1
Smoke Emission Test to IEC 61034
Operating Temperature ℃ 70
Velocity of propagation 74%
Impedance(ohm)     100±15

website: www.caledonian-cables.com